Wire Gauge Cross Reference

(Stranded Wire Only)

AWG

American
Wire Gauge

MCM

Approximate Diameter

Ohm/Mft

(copper only)

Amps
(Free Air)

*

MM2

20

 

 

 

 

0.52

18

1620

0.040in/1mm

7.77

 

1.0

16

2580

0.051in/1.25mm

4.89

 

1.5

14

4110

0.064in/1.6mm

3.07

25

2.5

12

6530

0.081in/2mm

1.93

30

4.0

10

10380

0.102in/2.5mm

1.21

40

6.0

8

16510

0.128in/3.25mm

0.764

60

10.0

6

26240

0.184in/4.6mm

0.491

80

16.0

4

41740

0.232in/5.9mm

0.308

105

25.0

2

66360

0.292in/7.4mm

0.194

140

35.0

1

83690

0.332in/8.4mm

0.154

165

40.0

1/0

105600

0.373in/9.5mm

0.122

195

53.5

2/0

133100

0.419in/10.6mm

0.0967

225

70.0

3/0

167800

0.470in/12mm

0.0766

260

95.0

4/0

211600

0.528in/13.4mm

0.0608

300

120.00

300 MCM

300,000

0.630in/16mm

0.0429

375

150

350 MCM

350,000

0.681in/17.25mm

0.0367

420

185

500 MCM

500,000

0.813in/20.65mm

0.0258

515

240

600 MCM

600,000

0.893in/22.68mm

0.0214

575

300

750 MCM

750,000

0.998in/25mm

0.0171

655

400

1000 MCM

1,000,000

1.150in/29.25mm

0.0129

780

500

*Based on single insulated conductor in free air at 30 degree temperature rise.